Wireless Tunnel™ Radio Sensor based on LoRa™ Technology
Temperature and Humidity Monitoring
Monitor temperature and humidity in cabinets, refrigerators and rooms. With the integrated door contact sensor you are also able to keep track of your security condition, or ignore temperature fluctuations when the door is opened. IP66 rated enclosure provides weatherproofing for use in outdoor environments. Easy installation and pairing with AKCP Wireless Tunnel™ Gateway.
Sensor Features
- 4x AA Batteries, with 10 year battery life*M
- 5VDC or 12VDC powered
- IP66 Waterproof enclosure
- Custom cable lengths to position sensor and antenna in optimal position.
Wireless Tunnel™ Monitoring Solutions
*10 year battery life based on data broadcast once every 15 minutes at an ambient temperature of 25°C
Sensor Type |
Temperature and Humidity Sensor Security Sensor (magnetic switch) |
Status Indication | LED indication for – Mode – Status – RSSI |
Components |
Manufactured using highly integrated, low power surface mount technology to ensure long term reliability. |
Operating Environment |
Temperature : Min. -35° C – Max.80° C Humidity: Min. 20% – Max. 80% (Non-Condensing) |
LoRa (R) Radio Regional plans |
– EU868 : 863~868Mhz, Max TX Power +14dBm, Duty Cycle 1% – US915: 903~915Mhz, Max TX Power +17dBm – AS923 : 920~925Mhz, Max TX Power +14dBm, Duty Cycle 1% – KR920 (Korea) : 922~923Mhz, Max TX Power +14dBm, Duty Cycle 1% – IL917 (Israel) : 915~917Mhz , Max TX Power +14dBm, Duty Cycle 1% |
Certification |
FCC Part15C, CE EN300220-2 |
Interface |
Micro-USB port for powering, adding and upgrading to the Gateway base unit |
Dimension |
76 x 77 x 120mm |
Mounting |
Wall hanging, DIN rail, Pipe Clamp |
Power source |
4xAA batteries or via micro-USB port |
Power Consumption |
Average 12 mWatt, 10uA in Idle, up to 10 years battery life |
Environment monitoring |
|
Temperature |
|
Measurement Range |
-40°C to +75°C -40°F to +167°F |
Measurement Resolution | 0.1°C increments 0.2°F increments |
Measurement Accuracy |
Typical : * ±0.3 from -40ºC to +75ºC * ±0.4 from -40ºF to +167ºF Maximum : * ±0.4 at -40ºC and ±0.4 at +75ºC * ±0.7 at -40ºF and ±0.7 at +167ºF |
Humidity | |
Measurement range | 0 to 100% Relative humidity |
Resolution | 1%RH increments, 0.01%RH sensor reading |
Accuracy at | 25°C ±2%RH |
Security Sensor | Switch type dry contact: open or close Dry contact counter |
Input | 0 to 100% Relative humidity |
Gateway sensor count |
7 (3 + 4) |