AKCP Sensor Adapter
Connect analog sensors with 0-10 VDC output, and dry contact sensors that require constant 5 VDC power.
The Sensor Adapter makes it easy to connect third-party analog sensors that output a 0-10 DC Voltage scale.
A switch on the side of the sensor adapter allows you to switch to a dry contact I/O instead, which is capable of maintaining a 5VDC output to power the sensor at all times, while still monitoring the dry contact input.
- Product Code: SEN-A
Specifications
Measuring Specifications | |
Configuration | Selectable type, with autosense setting : + 0~10 VDC + Dry Contact Input/Output |
Connector | 3 pin phoenix connector + Voltage Input : Signal, 5V, GND + Dry Contact : Dry Contact, 5V, GND |
Electrical | no galvanic isolation can provide up to 5V 0.2A for 3rd party device powering |
Interface | |
Communications cable | RJ-45 jack to sensor using UTP CAT5e/6 cable |
Power source | Powered by the controller unit. No additional power needed |
Power Consumption | Typical 50 mWatt, 10 mA |
Maximum Cable Length | The Sensor Adaptor can be extended from the RJ-45 Intelligent Sensor ports on the base units up to 50 feet, or 15 meters using standard CAT5/6 LAN cable |
Components | Manufactured using highly integrated, low power surface mount technology to ensure long term reliability. |
Operating Environment | Temperature : Min. -35° C – Max.80° C Humidity: Min. 20% – Max. 80% (Non-Condensing) |
Dimensions | 56 x 55 x 33.3 mm |
Mounting | DIN rail mounting Screw mounting |
Sensor count | 1 |